ม เตอร อ านไฟฟ า accuenergy model acuvim

16" Long Rogowski Coil CT with 4" Window; Calibrated for 5A- 1200A + $90.00

16" Long Rogowski Coil CT with 4" Window; Calibrated for 12.5A- 3000A + $90.00

16" Long Rogowski Coil CT with 4" Window; Calibrated for 25A-6000A + $90.00

24" Long Rogowski Coil CT with 7" Window; Calibrated for 5A-1200A + $112.00

24" Long Rogowski Coil CT with 7" Window; Calibrated for 12.5A-3000A + $112.00

24" Long Rogowski Coil CT with 7" Window; Calibrated for 25A-6000A + $112.00

36" Long Rogowski Coil CT with 10.67" Window; Calibrated for 5A-1200A + $162.00

36" Long Rogowski Coil CT with 10.67" Window; Calibrated for 12.5A-3000A + $162.00

36" Long Rogowski Coil CT with 10.67" Window; Calibrated for 25A-6000A + $162.00

47" Long Rogowski Coil CT with 14.5" Window; Calibrated for 5A-1200A + $255.00

47" Long Rogowski Coil CT with 14.5" Window; Calibrated for 12.5A-3000A + $255.00

47" Long Rogowski Coil CT with 14.5" Window; Calibrated for 25A-6000A + $255.00

250:5A Split Core CT, 0.83" * 1.22" Window Size + $53.60

1000:5A Split Core CT, 2.0" * 3.15" Window Size + $83.80

1000:5A Split Core CT, 3.15" * 4.72" Window Size + $98.05

2000:5A Split Core CT, 3.15" * 6.3" Window Size + $127.20

2500:5A Split Core CT, 3.15" * 6.3" Window Size + $132.20

5000:5A Split Core CT, 3.15" * 6.3" Window Size + $162.20

The Acuvim II Series power and energy meters are the simple, robust solution for power monitoring, kWh metering, power quality analysis, and more. This multifunction meter is engineered for easy integration into any project environment and a wide array of plug-in expansion modules facilitate communication on over 15 different industry-standard protocols.

  • Revenue grade: ANSI C12.20 class 0.2 & IEC 62053-22 class 0.2s
  • Data Logging available in 8MB, 16MB, 4GB, and 8GB with WEB2 module
  • Modbus-RTU & DNP 3.0 ready. Optional modules add support for multiple industrial protocols & interfaces such as Modbus, BACnet, IEC 61850, WiFi, and Ethernet
  • Available compatibility with multiple CT output options including 5A, mA, RCT (Rogowski), or 333mV
  • Designed with industry-leading cybersecurity and an anti-tampering seal
  • Configure as a panel-mount meter with digital display or DIN rail mount transducer
  • 5-year warranty

Related Categories

The Accuenergy Acuvim IIR revenue-grade power/energy meter with data logging can be a powerful tool for monitoring the energy consumption of a property, which can provide both accurate billing for tenants while helping identify areas to implement energy efficiency upgrades. This model includes the Acuvim IIR basic unit with field selectable 5A or 1A current input, 100 to 415V AC, 50/60Hz, 100 to 300V DC power supply, and an integrated mounting option with LCD display.

Functions

ม เตอร อ านไฟฟ า accuenergy model acuvim
ม เตอร อ านไฟฟ า accuenergy model acuvim
ม เตอร อ านไฟฟ า accuenergy model acuvim
ม เตอร อ านไฟฟ า accuenergy model acuvim

Features

  • Revenue grade ANSI C12.20 class 0.2 & IEC 62053-22 class 0.2s
  • 100ms refresh rate
  • Over/Under limit alarms
  • Web server and email sending
  • Switch status monitoring
  • Built-in MODBUS RTU via RS485 port
  • Can be upgraded to include Modbus TCP Ethernet, BACnet, Profibus, and a variety of other communication protocols and I/O expansions for added versatility
  • Onboard data logging memory is up to 8 MB and each log size is adjustable
  • Real time clock allows for any logged events to be accurately time stamped

Acuvim IIR Specifications

Accuracy Acuvim-II Accuracy Acuvim-IIR/IIE/IIW Resolution Range Voltage 0.2% 0.2% 0.1V 20V~1000kV Current 0.2% 0.2% 0.1mA 5mA~50000A Power 0.5% 0.2% 1W -9999MW~9999MW Reactive Power 0.5% 0.2% 1var 9999Mvar~9999Mvar Apparent Power 0.5% 0.2% 1VA 0~9999MVA Power Demand 0.5% 0.2% 1W -9999MW~9999MW Reactive Power Demand 0.5% 0.2% 1var -9999Mvar~9999Mvar Apparent Power Demand 0.5% 0.2% 0.2% 0~9999MVA Power Factor 0.5% 0.2% 0.001 -1.000~1.000 Frequency 0.2% 0.2% 0.01Hz 45.00~65.00Hz Energy Primary 0.5% 0.2% 0.1kWh 0-99999999.9kWh Energy Secondary 0.5% 0.2% 0.001kWh 0-999999.999kWh Reactive Energy Primary 0.5% 0.2% 0.1kvarh 0-99999999.9kvarh Reactive Energy Secondary 0.5% 0.2% 0.001kvarh 0-999999.999kvarh Apparent Energy Primary 0.5% 0.2% 0.1kVAh 0-99999999.9kVAh Apparent Energy Secondary 0.5% 0.2% 0.001kVAh 0-999999.999kVAh Harmonics 1.0% 1.0% 0.1% 0.0%~100.0% 20.0%~100.0% (IIR/IIE/IIW) Phase Angle 2.0% 2.0% 0.1° 0.0°~359.9° Unbalance Factor 2.0% 2.0% 0.1% 0.0%~100.0% Running Time 0.01h 0~9999999.99h Current Inputs (Each Channel) Nominal Current 5A /1A Metering Range 0~10A AC Withstand 20Arms continuous, 100Arms for 1 second, non-recurring Burden 0.05VA (typical) @ 5Arms Pickup Current 0.1% of nominal Accuracy 0.2% full scale Voltage Inputs (Each Channel) Nominal Full Scale 400V AC L-N, 690V AC L-L (+20%) Withstand 1500V AC continuous 2500V AC, 50/60Hz for 1 minute Input Impedance 2Mohm per phase Metering Frequency 45Hz~65Hz Pickup Voltage 10V AC (30V AC for Acuvim IIR/IIE/IIW) Accuracy 0.2% full scale Energy Accuracy (Acuvim IIR/IIE/IIW) Active According to IEC 62053-22: Class 0.2s According to ANSI C12.20: Class 0.2s Reactive (according to IEC 62053-23) Class 2 Harmonic Resolution Metered Value Acuvim II: 31st harmonic Acuvim IIR/IIE/IIW: 63rd harmonic Control Power Universal AC or DC Operating Range 100~415V AC, 50/60Hz 100~300V DC Burden 5W Frequency 50/60Hz Withstand 3250V AC, 50/60Hz for 1 minute Installation Category III (Distribution) Low Voltage DC Control Power (Optional) Operating Range 20~60V DC Burden 5W

Communication

Rs-485 (standard) MODBUS® RTU Protocol, 2-wire connection 1200~38400 baud rate

The second Rs-485 Port (Optional) MODBUS® RTU Protocol, 2-wire connection 4800~38400 baud rate

Ethernet (Optional) 10M/100M BaseT MODBUS® TCP/IP Protocol Data Browsing through HTTP Sending e-mail automatically

PROFI-BUs (Optional) PROFIBUS-DP/V0 Protoco Work as PROFIBUS slave, baud rate adaptive, up to 12M Typical input bytes: 32, typical output bytes: 32 PROFIBUS standard according to EN 50170 vol.2

Click here for complete specifications on the Accuenergy Acuvim IIR-D-5A-P1V3

What's included with the Accuenergy Acuvim IIR-D-5A-P1V3

  • Accuenergy Acuvim IIR-D-5A-P1V3 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc

Acuvim II Series Comparison

Category Item Parameters Acuvim II Acuvim IIR Acuvim IIE Acuvim IIW Metering Real Time Metering Phase Voltage V1, V2, V3, Vlnavg Metering Real Time Metering Line Voltage V12, V23, V31, Vllavg Metering Real Time Metering Current I1, I2, I3, In, Iavg Metering Real Time Metering Power P1, P2, P3, Psum Metering Real Time Metering Reactive Power Q1, Q2, Q3, Qsum Metering Real Time Metering Apparent Power S1, S2, S3, Ssum Metering Real Time Metering Power Factor PF1, PF2, PF3, PF Metering Real Time Metering Frequency F Metering Real Time Metering Load Features Load Features Metering Real Time Metering Four Quadrant Powers Four Quadrant Powers Metering Energy & Demand Energy Ep_imp, Ep_exp, Ep_total, Ep_net Metering Energy & Demand Reactive Energy Eq_imp, Eq_exp, Eq_total, Eq_net Metering Energy & Demand Apparent Energy Es Metering Energy & Demand Demand Dmd_P, Dmd_Q, Dmd_S, Dmd_I1, Dmd_I2, Dmd_I3 TOU Time of Use Energy/max demand TOU, 4 Tariffs, 12 Seasons, 14 Schedules TOU Daylight Savings Time Two formats adjust Month/Day/Hour/Minute Month/Week/First few weeks/Hour/Minute Monitoring Waveform Capture voltage and current Waveform Trigger, Manual, DI change, Sag/Dips, Swell, Over Current Monitoring Power Quality Voltage Unbalance Factor U_unbl Monitoring Power Quality Current Unbalance Factor I_unbl Monitoring Power Quality Voltage THD THD_V1,THD_V2,THD_V3, THD_Vavg Monitoring Power Quality Current THD THD_I1, THD_I2, THD_I, THD_Iavg Monitoring Power Quality Individual Harmonics Harmonics 2nd to 63rd (31st for Acuvim II) Monitoring Power Quality Voltage Crest Factor Crest Factor Monitoring Power Quality TIF THFF Monitoring Power Quality Current K factor K Factor Monitoring Statistics MAX with Time Stamp MIN with Time Stamp Each phase of V & l; Total of P, Q, S, PF & F; Demad of P,Q & S; Each phase THD of V & I; Unbalnce factor of V & I Others Alarm Over/Under Limit Alarm V, I, P, Q, S, PF, V_THD & I_THD each phase and total or average; Unbalance factor of V & I; load type; Analog Input of each channel Others Power Quality Event logging SAG/DIPS,SWELL Voltage Others Data Logging Data Logging 1 Data Logging 2 Data Logging 3 F, V1/2/3/lnavg, V12/23/13/lavg, I1/2/3/n/avg, P1/2/3/sum,Q1/2/3/sum, S1/2/3/sum, PF1/2/3, PF, U_unbl, I_unbl, LoadType, Ep_imp, Ep_exp, Ep_total, Ep_net, Eq_imp, Eq_exp, Eq_total, Eq_net, Es, THD_V1/2/3/avg, THD_I1/2/3/avg, Harmonics2nd to 63rd, Crest Factor, THFF, K Factor, sequence and phaseangles, DI counter, AI, AO, Dmd P/Q/S, Dmd I1/2/3 Others Onboard memory size Memory Bytes - 4MB 4MB 8MB Others Communication RS485 Port, Half Duplex,Optical Isolated Modbus®-RTU Protocol Others Time Real Time Clock Year, Month, Date, Hour, Minute, Second Option Module I/O Option Switch Status (DI) Digital Input (Wet) Option Option Option Option Option Module I/O Option Power Supply for DI 24 Vdc Option Option Option Option Option Module I/O Option Relay Output (RO) NO, Form A Option Option Option Option Option Module I/O Option Digital Output (DO) Photo-MOS Option Option Option Option Option Module I/O Option Pulse Output (PO) By using DO Option Option Option Option Option Module I/O Option Analog Input (AI) 0(4)~20mA, 0(1)~5V Option Option Option Option Option Module I/O Option Analog Output (AO) 0(4)~20mA, 0(1)~5V Option Option Option Option Option Module Communication Ethernet 10M/100M, Modbus-TCP, HTTP Webpage, Email Option Option Option Option Option Module Communication Profibus-DP Profibus-DP/V0 Option Option Option Option Option Module Communication RS485 Module Additional Modbus RTU Option Option Option Option

Acuview Software

As the need to better understand power and energy consumption increases, Accuenergy continues to offer a simple and effective software compliment to our metering products. Combining their meters with the Acuview software suite allows Accuenergy to offer one of the most powerful yet cost effective metering and monitoring solutions in the market.

Acuview Software Features

  • Simple setup feature for fast deployment and configuration of Accuenergy meters
  • Remote and real time monitoring of all meter parameters
  • Dozens of meters can be connected to a single PC
  • Multiple meters can be displayed and tiled in one window
  • Real time data logging
  • Logging of data from the I/O modules (pulses from water, gas, flow, etc)
  • All data logged into simple and easy to read Excel spreadsheets (.xls, .csv or .txt formats)
  • SmartSum feature provides aggregate Energy & Demand data for an average of the entire system being monitored

Accessories

Click on a category to view a selection of compatible accessories with the Accuenergy Acuvim IIR-D-5A-P1V3 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc.

ม เตอร อ านไฟฟ า accuenergy model acuvim

Acuvim AXM-IO1 Digital/Analog I/O Module 6DI, 1 Power Supply for DI, 2RO AXM-IO1

This plug-in I/O module integrates data to/from other devices and is field expandable. It provides added functions and increased versatility for any of the Avuvim II Series. These increased functions can be enabled by simply snapping on the module to the back of either meter and can work in conjunction with two other extension modules (cannot be paired with the same module). This module features 6 Digital Inputs, 24V DC Power for Digital Inputs, and 2x Relay Outputs.


ม เตอร อ านไฟฟ า accuenergy model acuvim

Acuvim AXM-IO2 Digital/Analog I/O Module 4DI, 2DO, 2AO AXM-IO2

This plug-in I/O module integrates data to/from other devices and is field expandable. It provides added functions and increased versatility for any of the Avuvim II Series. These increased functions can be enabled by simply snapping on the module to the back of either meter and can work in conjunction with two other extension modules (cannot be paired with the same module). This module features 4 Digital Inputs, 2 Digital Outputs, and 2 Analog Outputs of 4 to 10mA.


ม เตอร อ านไฟฟ า accuenergy model acuvim

Acuvim AXM-IO3 Digital/Analog I/O Module 4DI, 2RO, 2AI AXM-IO3

This plug-in I/O module integrates data to/from other devices and is field expandable. It provides added functions and increased versatility for any of the Avuvim II Series. These increased functions can be enabled by simply snapping on the module to the back of either meter and can work in conjunction with two other extension modules (cannot be paired with the same module). This module features 4 Digital Inputs, 2 Relay Outputs, and 2 Analog Inputs of 4 to 10mA.


ม เตอร อ านไฟฟ า accuenergy model acuvim


ม เตอร อ านไฟฟ า accuenergy model acuvim

Accuenergy AXM-WEB Ethernet Module for Acuvim II AXM-WEB

Provides an Ethernet connection to the Acuvim II Series power meters via Modbus-TCP/IP, HTTP Post, HTTPS Post, FTP, SMTP for e-mail, and SNTP time synchronization. Features 4GB onboard memory with 15-second interval data logging capabilities, and industry-leading 100ms response rate via ModbusTCP/IP protocol.